Number of credits available | Minimum standards |
---|---|
Building type dependent |
No |
To ensure daylighting, artificial lighting and occupant controls are considered at the design stage to ensure best practice in visual performance and comfort for building occupants.
This issue is split into four parts:
The following is required to demonstrate compliance:
AND
OR
Building/area type | Credits | Average daylight factor required | Minimum area (m²) to comply | Other requirements |
---|---|---|---|---|
Education buildings | ||||
Pre-schools, schools, further education- occupied spaces |
2 | 2% | 80% | EITHER (a) OR {(b) and (c)} in Table 11 |
Higher education- occupied spaces |
1 | 2% | 60% | |
2 | 2% | 80% | ||
Healthcare buildings | ||||
Staff and public areas |
2 | 2% | 80% |
EITHER (a) OR {(b) and (c)} in Table 11 |
Occupied patient’s areas (dayrooms, wards) and consulting rooms | 3% | 80% | ||
Multi-residential buildings | ||||
Kitchen |
1 | 2% | 80% | EITHER (a) OR (c) in Table 11 |
Living rooms, dining rooms, studies (including home office) |
2 % | 80% | ||
Non-residential or communal occupied spaces |
2% | 80% | ||
Retail buildings | ||||
Sales areas | 1 | - | 35% | Point daylight factors of 2% or more |
Other occupied areas | 1 | 2% | 80% | EITHER (a) OR {(b) and (c)} in Table 11 |
Courts, Industrial, Office, Prison buildings and all Other building types | ||||
Cells and custody cells | 1 | 1.5% | 80% | N/A |
Internal association or atrium area | 3% | 80% | EITHER a uniformity ratio of at least 0.7 OR a minimum point daylight factor of 2.1% | |
Patient care spaces | 3% | 80% | EITHER (a) OR {(b) and (c)} in Table 11 | |
Teaching, lecture and seminar spaces | 2% | 80% | EITHER (a) OR {(b) and (c)} in Table 11 | |
All occupied spaces, unless indicated in Hea 01 Visual comfort | 2% | 80% | EITHER (a) OR {(b) and (c)} in Table 11 |
Ref | Criteria |
---|---|
(a) |
A uniformity ratio of at least 0.3 or a minimum point daylight factor of at least 0.3 times the relevant average daylight factor value in Table 10 . Spaces with glazed roofs, such as atria, must achieve a uniformity ratio of at least 0.7 or a minimum point daylight factor of at least 0.7 times the relevant average daylight factor value in Table 10 . |
(b) | At least 80% of the room has a view of sky from desk or table top height (0.85m in multi-residential buildings, 0.7m in other buildings). |
(c) |
The room depth criterion d/w +d/HW < 2/(1-RB) is satisfied. Where: d = room depth, w = room width, HW = window head height from floor level, RB = average reflectance of surfaces in the rear half of the room, Note: Table 17 gives maximum room depths in metres for different room widths and window head heights of side-lit rooms |
Area type | Credits | Minimum area to comply | Average daylight illuminance (averaged over entire space) | Minimum daylight illuminance at worst lit point |
---|---|---|---|---|
Education buildings | ||||
Pre-schools, schools, further education - occupied spaces |
2 | 80% | At least 300 lux for 2000 hours per year or more | At least 90 lux for 2000 hours per year or more |
Higher education - occupied spaces | 1 | 60% | ||
OR Higher education - occupied spaces | 2 | 80% | ||
Healthcare buildings | ||||
Staff and public areas | 2 | 80% | At least 300 lux for 2000 hours per year or more | At least 90 lux for 2000 hours per year or more |
Occupied patient's areas (dayrooms, wards) and consulting rooms | 80% | At least 300 lux for 2650 hours per year or more | At least 90 lux for 2650 hours per year or more | |
Multi-residential buildings | ||||
Kitchen |
1 | 100% | At least 100 lux for 3450 hours per year or more | At least 30 lux for 3450 hours per year or more |
Living rooms, dining rooms, studies (including home office) |
At least 100 lux for 3450 hours per year or more | At least 30 lux for 3450 hours per year or more | ||
Non-residential/communal occupied spaces |
80% | At least 200 lux for 2650 hours per year or more | At least 60 lux for 2650 hours per year or more | |
Retail buildings | ||||
Sales areas |
1 | 35% | At least 200 lux point daylight illuminances for 2650 hours per year or more | |
Other occupied areas |
1 | 80% | At least 200 lux for 2650 hours per year or more | At least 60 lux for 2650 hours per year or more |
Courts, Industrial, Office, Prison buildings and all Other building types | ||||
Cells and custody cells | 1 | 80% | At least 100 lux for 3150 hours per year or more | N/A |
Internal association or atrium | 80% | At least 300 lux for 2650 hours per year or more | At least 210 lux for 2650 hours per year | |
Patient care spaces | 80% | At least 300 lux for 2650 hours per year or more | At least 210 lux for 2650 hours per year or more | |
Teaching, lecture and seminar spaces | 80% | At least 300 lux for 2000 hours per year or more | At least 90 lux for 2000 hours per year or more | |
All occupied spaces, unless indicated in Relevant definitions | 80% | At least 300 lux for 2000 hours per year or more | At least 90 lux for 2000 hours per year or more |
Building type | View out requirements |
---|---|
Prison buildings |
Cells An adequate view out from a normal standing or sitting position and the distance between each window and nearest external solid object (i.e. buildings, screens, walls/fences) is ≥ 10m. Where existing features prevent compliance with this criteria in less than 20% of the cells within the building, the credit can still be awarded. Patient occupied spaces See Healthcare requirements for these spaces. |
Multi-residential buildings |
Self-contained flats - living rooms Sheltered housing - communal lounges, individual bedrooms and bedsits All positions within relevant areas are to be within 5m of a wall which has a window or permanent opening providing an adequate view out. The window/opening must be ≥ 20% of the surrounding wall area. |
Healthcare buildings with inpatient areas (one additional credit) |
Patient occupied spaces, e.g. wards and dayrooms As criteria 4 and 5 for the relevant building areas PLUS the distance between the wall with the window/opening and nearest external solid object (e.g. buildings, screens, walls/fences) is ≥ 10m. |
Note: the criteria for zoning of lighting control are excluded for assessments of prison buildings.
Building type | Internal and external lighting requirements |
---|---|
Education buildings | Manual lighting controls are easily accessible for the teacher while teaching and on entering/leaving the teaching space. |
Prison buildings |
Cells Lit to a maintained illuminance of 200 lux at table top level. In addition there must be the facility (using, for example, dimming, step switching or separate task and general lighting) for the occupant of the cell to select a lower level of general lighting if required. Exercise yards Lit to a maintained illuminance of at least 10 lux. However, if such spaces are, or will be, used as sports facilities they must be lit to a maintained illuminance of 100 lux. |
Court buildings |
Separate zoning is also provided for the following areas (as a minimum):
Lighting control of the zones in the above spaces, and the courtroom as a whole, cater for the following settings:
|
The following outlines the exemplary level criteria to achieve an innovation credit for daylighting:
OR
Area type | Credits | Average daylight factor required |
Minimum area (m2) to comply |
Other requirements |
---|---|---|---|---|
All building types | The criteria outlined in Table 10 and Table 11 concerning uniformity ratio (a), view of sky (b) or room depth criterion (c) are met where they are used to demonstrate compliance. | |||
All building types (excluding retail – see below) | ||||
Functions as identified in the standard criteria (multi storey buildings) | 1 | 3% | 80% | Where used, a minimum point daylight factor of 1.2% OR 2.1% for spaces with glazed roofs, such as atria |
Functions as identified in the standard criteria (single storey buildings) | 4% | 80% | Where used, a minimum point daylight factor of 1.6% OR 2.8% for spaces with glazed roofs, such as atria | |
Prisons and court cells | 2% | 80% | N/A | |
Prison internal association/atrium area | 5% | 80% | A uniformity ratio of at least 0.7 or a minimum point daylight factor of 3.5% | |
Retail | ||||
Sales areas | 1 | N/A | 50% | A minimum point daylight factor of 2% must be achieved in the compliant areas. Assess total sales areas without rounding up to the nearest room. |
Common areas and offices (multi storey buildings) | 3% | 80% | Where used, a minimum point daylight factor of 1.2% OR 2.1% for spaces with glazed roofs, such as atria | |
Common areas and offices (single storey buildings) | 4% | 80% | Where used, a minimum point daylight factor of 1.6% OR 2.8% for spaces with glazed roofs, such as atria |
Area type | Credits | Minimum area to comply | Average daylight illuminance (averaged over entire space) | Minimum daylight illuminance at worst lit point |
---|---|---|---|---|
All building types (excluding retail – see below) | ||||
Multi-storey buildings Occupied spaces (unless indicated below) |
1 | 80% | At least 300 lux for 2650 hours per year or more | At least 90 lux for 2650 hours per year or more |
Single storey buildings Occupied spaces (unless indicated below) |
80% | At least 300 lux for 3000 hours per year or more |
At least 120 lux for 3000 hours per year or more; or in spaces with glazed roofs (such as atria), at least 210 lux for 3000 hours per year or more |
|
Prisons and courts buildings Cells and custody cells |
80% | At least 100 lux for 3450 hours per year or more | N/A | |
Prison buildings Internal association or atrium areas |
80% | At least 300 lux for 3250 hours per year or more | At least 210 lux for 3250 hours per year or more | |
Retail | ||||
Retail buildings Sales areas |
1 | 50% | At least 300 lux point daylight illuminances for 2000 hours per year or more | |
Retail buildings Other occupied areas |
80% | Select relevant criteria above for occupied spaces dependant on whether you are assessing a multi-storey or single- storey building. |
The table below gives maximum room depths in metres for different room widths and window head heights of side-lit rooms.
Reflectance (RB) |
0.4 | 0.5 | 0.6 | |||
---|---|---|---|---|---|---|
Room width (m) | 3 | 10 | 3 | 10 | 3 | 10 |
Window head height (m) | ||||||
2.5 | 4.5 | 6.7 | 5.4 | 8.0 | 6.8 | 10.0 |
3.0 | 5.0 | 7.7 | 6.0 | 9.2 | 7.5 | 11.5 |
3.5 | 5.4 | 8.6 | 6.5 | 10.4 | 8.1 | 13.0 |
Ref |
Terms |
Description |
---|---|---|
Shell and core | ||
CN1 |
Applicable assessment criteria |
Glare control, criteria 1 to 2 Both options :These criteria are not applicable. Daylighting, criteria 3 and 14 Both options : All criteria relevant to the building type and function apply. View out, criteria 4 to 6 Both options: All criteria relevant to the building type and function apply. Internal lighting, zoning and occupant control, criteria 7 to 9, 11 to 13 Both options : These criteria are not applicable. External lighting, criteria 10, 13 Both options: All criteria relevant to the building type and function apply. Refer to Appendix D – BREEAM UK New Construction and Shell and Core Project Assessments for a more detailed description of the above shell and core assessment options. |
CN1.1 |
Glare control | This compliance note has been removed as the Glare control credit is not applicable to Shell only and Shell and core assessments. |
CN1.2 |
View out |
Both options Where it is not possible to confirm which areas of the building will contain workstations/benches or desks, then all areas of the building designed for and/or likely to be occupied by workstations/benches or desks must comply with the relevant criteria. |
Simple buildings | ||
CN2 |
Applicable assessment criteria | All criteria relevant to the building type and function apply. |
General | ||
Glare control | ||
Compliant forms of glare control - curtains as glare control |
Compliant shading measures for meeting glare control credit include:
Glare control must provide shading from both high level summer and low level winter sun. Where using fixed systems, design studies can be used to demonstrate that sunlight is prevented from reaching building occupants during occupied hours. Curtains (where used without other forms of shading) do not meet the criteria for the glare control credit, as they do not provide sufficient control to optimise daylight in to the space. Furthermore, the use of curtains to control glare is likely to cause occupants to rely more on artificial lighting. |
|
Daylighting | ||
CN3.1 |
Percentage of assessed area See criterion 3. |
Where the criteria specify that a percentage of floor area must be adequately illuminated by daylight, this refers to the percentage of the total floor area of all the rooms that must be assessed, i.e. the compliant area. If for example, a development has six rooms that must be assessed, each 150m² (total area 900m²) and 80% of this floor area must meet the criterion, then 720m² must comply with the criterion; this is equal to 4.8 rooms. The number of rooms that must comply must always be rounded up; therefore in this example, five rooms must have an average daylight factor of 2% or more (plus meet the other criteria) to achieve the credit. When using the point daylight factor to determine compliance for retail sales areas, the minimum percentage area should be based on the total floor area being assessed. Individual 'rooms' or sub areas do not need to meet the minimum thresholds. This is to allow for the typical building form restrictions and layout configurations that are necessary for these type of spaces. |
CN3.2 |
External obstructions | In calculating minimum and average daylight factors and daylight illuminances, external obstructions should be taken into account. For illuminance calculations, the reflectance of external obstructions should be taken as 0.2 unless on-site measurements of external reflectance have been made. |
CN3.3 |
Dirt factors when calculating daylight | Daylight calculations should include a maintenance factor for dirt on the windows, as given in British Standard Code of Practice for daylighting, BS8206 Part 2, appendix A1.3. |
CN3.4 |
Borrowed light | For areas where borrowed light is used to demonstrate compliance with daylighting criteria, calculations or results from appropriate lighting design software must be provided to demonstrate that such areas meet the BREEAM criteria (if the light from these sources is required in order for the room to comply). Examples of borrowed light include: light shelves, clerestory glazing, sun pipes or internal translucent/transparent partitions (such as those using frosted glass). |
CN3.5 |
Room depth criterion - rooms lit from two opposite sides | For rooms lit by windows on two opposite sides, the maximum room depth that can be satisfactorily illuminated by daylight is twice the limiting room depth (d) (measured from window wall to window wall; CIBSE Lighting Guide LG105CIBSE Lighting Guide LG10 Daylighting and window design, 1999.. The reflectance of the imaginary internal wall should be taken as 1. |
CN3.6 |
Uniformity with rooflights | The room depth criteria cannot be used where the lighting strategy relies on rooflights. In such areas either appropriate software has to be used to calculate the uniformity ratio or, in the case of a regular array of rooflights across the whole of the space, figure 2.36 (page 37) within CIBSE Lighting Guide LG10 can be used to determine the uniformity ratio. |
CN3.7 |
Daylighting - uniformity ratio Calculation | The uniformity ratio calculation, minimum point daylight factor and minimum daylight illuminance can exclude areas within 0.5m of walls. Areas within 0.5m are not regarded as part of the working plane for this purpose, although they are included in the average daylight factor and average daylight illuminance calculations. |
CN3.8 |
View of sky requirement See criterion 3. |
To comply with the view of sky criteria (ref (b)) in Table 11 , at least 80% of the room that complies with the average daylight factor requirement must receive direct light from the sky, i.e. it is permissible for up to 20% of the room not to meet the view of sky requirement and still achieve a compliant room. |
Internal and external lighting levels/zoning and control | ||
CN3.9 |
Relevant industry standard for lighting design |
Pre-schools, schools and sixth form colleges: Building Bulletin 90: ‘Lighting Design for Schools’6Building Bulletin 90: ‘Lighting Design for Schools’ Please note that for care homes housing people with dementia the following standard can be used instead of the SLL Code for Lighting:
Please note that the illuminance levels specified in the SLL Code for Lighting, 2012 align with BS EN 12464-18BS EN 12464-1:2014 Light and lighting. Lighting of work places. Indoor work places, 2003. |
CN3.10 |
Occupancy/ workstation layout unknown | Where occupancy or workstation layout is not known, lighting control can be zoned on the basis of 40m² grids, i.e. an assumption of 1 person/workspace per 10m². |
CN3.11 |
Small spaces | Buildings consisting entirely of small rooms/spaces (less than 40m²) which do not require any subdivision of lighting zones/control will meet the zoning criteria by default. |
CN3.12 |
Zones of four workspaces | The limit of four workspaces is indicative of the required standard but is not a fixed requirement. Where there is justification for this to be increased to fit with the adopted lighting strategy, this may be accepted provided that the assessor is satisfied that the aim of this criterion is upheld, i.e. that there is suitable zoning/control of lighting to enable a reasonable degree of occupant control over lighting in their personable work area. The relevant design team member, e.g. lighting consultant, should set out how this is to be achieved in such an instance. |
CN3.13 |
Lighting zoning and control - auditoria spaces | The controls specified will depend on the size and use of the space but a typical auditorium or lecture theatre with stepped seating and a formal lectern/demonstration/performance area would typically be expected to have lighting controls as follows:
|
CN3.14 |
No external lighting |
Where no external light fittings are specified (either separate from or mounted on the external building façade or roof), the criteria relating to external lighting do not apply and the credit can be awarded on the basis of compliance with the internal lighting criteria. The following internal areas are excluded from the lighting zone requirements:
|
Building type specific | ||
CN4 |
Education - Education Funding Agency (EFA) requirements | For Education buildings, where the EFA daylighting requirements have been achieved, for all relevant rooms within the building (in accordance with Priority School Building Programme (PSBP) Authority Draft, Facilities Output Specification: Generic Design Brief by the Education Funding Agency, June 20139Priority School Building Programme PSBP Authority Draft, Facilities Output Specification: Generic Design Brief by the Education Funding Agency, June 2013), it can be assumed that the BREEAM daylighting requirements have also been met and therefore the two credits available for daylighting can be awarded by default. In this instance, evidence would need to be provided to demonstrate that the EFA requirements have been achieved. |
CN4.1 |
Education (pre-schools) and acute Special Educational Needs (SEN) controls for children |
Where child care and/or acute SEN spaces are included within the scope of the assessment, controls should be provided for the teacher/member of staff, i.e. it is not a necessity for the controls to be accessible to the children. Where nursery spaces are included within the scope of the assessment, controls should be provided for the member of staff, not the nursery school children. |
None.
Criteria | Interim design stage |
Final post construction stage
|
---|---|---|
All |
One or more of the appropriate evidence types listed in The BREEAM evidential requirements section can be used to demonstrate compliance with these criteria. |
|
3, 4 |
Daylighting calculations |
Refer to generic evidence requirement above |
None.
BREEAM UK New Construction non-domestic buildings technical manual 2014
Reference: SD5076 – Issue: 5.0
Date: 23/08/2016
Copyright © 2016 BRE Global. All rights reserved.